How to Setup On/Off Lights to indicate VSD Running Status

| 0

External On /Off lights can be used to indicate a VSDs running status by using the VSD Relay Outputs. In order to do that a Power Source can be connected to one of the VSD Relays with the Off Light connected to the Normally Closed Relay Output and the On Light connected to the Normally Open Relay Output. Using the Relay Output parameters, the Outputs can be controlled by the VSD Running Status by setting the following parameter:

  • When using Relay 1 (TA1-TB1-TC1), set b4-02 = 2
  • When using Relay 2 (TA2-TB2-TC2 or TA-TB-TC), set b4-03 = 2

Please Note: For Smaller Drives with only one set of Relays (TA-TB-TC), use the TA2-TB2-TC2 Relay parameter settings.

Relay On/Off Lights

Contact driving capacity:

  • 250 Vac, 3 A, COSø = 0.4
  • 30 Vdc, 1 A